Products > CMP T3CDS Cable Gland | Triton T3CDS

CMP T3CDS Cable Gland | Triton T3CDS

Globally Approved, Explosive Atmosphere Cable Gland

• Fully sequential, three step installation procedure
• Reduces installation times, cost & risk
• Direct & remote installation
• Unique compensating displacement seal system (CDS)
– Metal-to-metal installation every time regardless of cable diameter
• Designed to prevent Coldflow, see CMP Technical Document TS002
• Integral protected deluge seal
• Controlled outer ‘load retention’ seal
• Unique OSTG prevents overtightening
• -60°C to +130°C (standard), -20°C to 200°C (ThermEx option )
• Globally marked, IECEx, ATEX, UL & cCSAus
• EMC tested

† Grooved Cone (X) is predominantly used for Wire Braid (e.g. GSWB, TCWB), Steel Tape Armour (STA, DSTA) and Aluminium Strip Armour (ASA) but is also suitable for Single Wire Armour (SWA), Aluminium Wire Armour (AWA) and Pliable Wire Armour (PWA) if the range is outside that of the Stepped Cone (W).

Note: Grooved Cone (X) dimensions shown in the Cable Gland Selection Table below are for a double wire strand of braid armour cables. Tapes can also be doubled over. For cables that have only a single layer of armour such as SWA the clamping range should be used as shown in the table below.

Stepped (W) Cone is suitable for Single Wire Armour (SWA), or Aluminium Wire Armour (AWA) cables.

For under / oversized armour wires

For all types of Armoured Cables

Description

CMP T3CDS | EUTEX T3CDS Technical Info

CMP T3CDS are explosive atmosphere barrier double-seal universal cable glands that are suitable for terminating all types of armored cables. Certified by ATEX for safe glanding of cables in Class 1, Zone 1, potentially explosive atmospheres, they feature a metal-to-metal sealing system that reduces costs, risks, and installation time.

This type of cable gland is manufactured to meet a wide array of standards, specifications, and codes. Examples include:

ATEX Certificates

  • CML 18ATEX1326X
  • CML 18ATEX4318X

Approvals

  • LRS: 01/00172 (E3)
  • DNV: TAE00000Y
  • ABS: 20-LD1948801-PDA
  • BV: 43180/A1BV

UL Compliance Standards

  • UL 514B Ed 5
  • UL 50 Ed 11
  • UL 2225 Ed 4
  • UL60079-0, 1, 7

IECEx Certificates

  • IECEx SIR 13.0027X
  • IECEx CML 18.0183X

UL Certificates

  • E200163

Code of Protection

  • Class I, Zone 1, AEx e II

Compliance Standards

  • IEC 60079-0,1,7,15,31

The Triton CDS cable gland utilizes a double-sealing mechanism, which includes an integral protected deluge seal and a controlled outer load-retention seal. It’s designed with a three-step installation process.

Available construction materials include brass, electroless nickel-plated brass, stainless steel, and aluminum constructions. EUTEX International’s standard offering is nickel-plated brass. Optional accessories include locknuts, earth tags, serrated washers, entry thread seals, shrouds, and ingress discs.

Standard cable operating environments are -60°C to +130°C, whereas ThermEx options are 20°C to 200°C. Many applications can benefit from integrating Triton CDS cable glands into their processes.

  • Aerospace
  • Defense
  • Chemical
  • Mining
  • Minerals & Metals
  • Commercial Construction
  • Downstream Hydrocarbons
  • Food & Beverage
  • Industrial Energy
  • Onsite Utilities

  • Industrial Machinery
  • Laboratory and R&D
  • Life Sciences
  • Medical
  • Marine
  • Oil & Gas
  • Packaging
  • Power
  • Pulp & Paper
  • Textiles
  • Water & Wastewate

Your Explosive Cable Gland Source

EUTEX International is a leading provider of electric cables and accessories for demanding industrial use. With an ISO 9001:2015-certified Quality Management System, every product we supply is guaranteed to be durable, effective, and of the highest quality. Strategically positioned locations worldwide enable us to deliver the electrical products you need on time and within budget.

Feel free to contact us about Triton cable gland products. Our experts are standing by to answer your questions.

Technical

Design SpecificationBS 6121:Part 1:1989, IEC 62444, EN 62444
Mechanical Classifications*Impact = Level 8, Retention = Class D
Enclosure ProtectionIK10 to IEC 62262 (20 joules) Brass & Stainless Steel only
Electrical Classifications*Category B (Category A when used with braid, tape or pliable wire armour cables)
ATEX CertificateSIRA13ATEX1073X
SIRA13ATEX4079X
Code of ProtectionII 2G,II 1D, Ex d IIC Gb, Ex e IIC Gb, Ex ta IIIC Da,
II 3G Ex nR IIC Gc, I M2, Ex d I Mb, Ex e I Mb
Compliance StandardsEN60079-0,1,7,15,31
IECEx CertificateIECEx SIR 13.0028X
IECEx SIM 14.0007X
Code of ProtectionEx d IIC Gb, Ex e IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da, Ex d I Mb, Ex e I Mb
Compliance StandardsIEC 60079-0,1,7,15,31
cCSAus Certificate (20s16 – 90)1310517
CSAus Code of ProtectionClass I, Div 2, Groups A,B,C and D, Class II, Div 2, Groups E,F and G, Class III, Enclosure
Type 3, 4 and 4X,
Class I, Zone 1, AEx e II, AEx nR II
cCSA Code of ProtectionClass I, Div 2, Groups A,B,C and D, Class II, Div 2, Groups E,F and G, Class III, Enclosure
Type 3, 4 and 4X,
Ex d IIC, Ex e IIC, Ex nR II
Compliance StandardsCAN/CSA-C22.2 No 0, 18, 25, 30, 94, 174, CAN/CSA-E60079-0, 1, 7,
ANSI/UL 514B Ed 5, ANSI/UL 50 Ed 11, ANSI/UL 2225 Ed 4, UL60079-0, 1, 7
UL Certificate (20s16 – 90)E200163
Code of ProtectionClass I, Zone 1, AEx e II
Compliance StandardsUL514B
EAC Certificate (Formerly GOST R, K & B)C-GB.AA87.B.00487
UkrSEPROUA.TR.047.C.0644-15
NEPSI CertificateGYJ13.1141X , GYJ13.1283X
CCOE / PESO (India) CertificateP333688
INMETRO CertificateTÜV 11.0374X
RETIE Certificate03866
Marine ApprovalsLRS: 01/00172 (E4), DNV: TAE00000Y, ABS: 14-LD234401A-4-PDA, BV: 43180/A1
Ingress Protection Rating **IP66, IP67 & IP68
Deluge Protection ComplianceDTS01 : 91
Cable Gland MaterialBrass, Electroless Nickel Plated Brass, Aluminium, Stainless Steel
Seal MaterialCMP SOLO LSF Halogen Free Thermoset Elastomer
Cable TypeSingle Wire Armour (SWA), Aluminium Wire Armour (AWA), Pliable Wire Armour (PWA), Steel Tape Armour (STA), Aluminium Strip Armour (ASA), Screened Flexible (EMC) Wire Braid (e.g. CY/SY), Wire Braid Armour (e.g. SWB)
Armour ClampingReversible Armour Cone & AnyWay Universal Clamping Ring
Sealing TechniqueInner Bedding Sealing Ring: Compensating Displacement Seal (CDS), Outer Sheath Sealing Ring : Load Retention Seal (LRS)
Sealing Area(s)Cable Inner Bedding & Outer Cable Sheath
Optional AccessoriesLocknuts, Earth Tags, Serrated Washers, Entry Thread Seals, Shrouds,Ingress Discs
Optional Installation ToolsSpanners, Armour Former Tool

Product Table

Metric

Cable Gland SizeAvailable Entry Threads “C” (Alternate Metric Thread Lengths Available)Cable
Bedding
Diameter
“A”
Overall
Cable
Diameter
“B”
Armour RangeAcross
Flats
“D”
Across
Corners
“D”
Protrusion
Length “F”
Combined Ordering Reference
(*Brass Metric)
ShroudCable
Gland
Weight
(Kgs)
StandardOptionGrooved Cone (X)Stepped Cone (W)
MetricThread Length (Metric) “E”NPTThread Length
(NPT) “E”
NPTMinMaxMinMaxMinMaxMinMaxMaxMaxSizeTypeOrdering
Suffix
16M1615.03.18.66.113.10.31.00.81.2524.026.478.716T3CDS1RAPVC360.18
20S16M2015.0½”19.9¾”3.18.66.113.10.31.00.81.2524.026.478.720S16T3CDS1RAPVC360.20
20SM2015.0½”19.9¾”6.111.69.515.90.31.00.81.2524.026.478.720ST3CDS1RAPVC360.20
20M2015.0½”19.9¾”6.513.912.520.90.41.00.81.2530.533.676.220T3CDS1RAPVC060.28
25SM2515.0¾”20.21″11.119.914.022.00.41.21.251.637.541.388.825ST3CDS1RAPVC090.44
25M2515.0¾”20.21″11.119.918.226.20.41.21.251.637.541.388.725T3CDS1RAPVC090.44
32M3215.01″25.01 ¼”17.026.223.733.90.41.21.62.046.050.690.732T3CDS1RAPVC110.63
40M4015.01 ¼”25.61 ½”22.032.127.940.40.41.61.62.055.060.593.240T3CDS1RAPVC150.91
50SM5015.01 ½”26.12″29.538.135.246.70.41.62.02.560.066.0100.750ST3CDS1RAPVC181.12
50M5015.02″26.92 ½”35.644.040.453.00.61.62.02.570.177.1105.850T3CDS1RAPVC211.60
63SM6315.02″26.92 ½”40.149.945.659.40.61.62.02.575.082.5102.563ST3CDS1RAPVC231.73
63M6315.02 ½”39.93″47.255.954.665.80.61.62.02.580.088.0105.463T3CDS1RAPVC251.78
75SM7515.02 ½”39.93″52.861.959.072.00.61.62.02.590.099.0110.675ST3CDS1RAPVC282.57
75M7515.03″41.53 ½”59.167.966.778.40.61.62.53.0100.0110.0120.375T3CDS1RAPVC303.33
90M9024.03 ½”42.84″66.678.676.290.30.81.63.154.0115.0126.5138.990T3CDS1RAPVC324.87
100M10024.03 ½”42.84″76.090.986.1101.40.81.63.154.0127.0139.7128.2100T3CDS1RALSF334.97
115M11524.04″44.05″86.097.9101.5110.20.81.63.154.0138.0151.8161.3115T3CDS1RALSF347.72
130M13024.05″46.897.0114.9110.2123.20.81.63.154.0157.0172.7173.3130T3CDS1RALSF359.78
Dimensions displayed in millimeters unless otherwise stated

Imperial

Cable Gland SizeAvailable Entry Threads “C” (Alternate Metric Thread Lengths Available)Cable
Bedding
Diameter
“A”
Overall
Cable
Diameter
“B”
Armour RangeAcross
Flats
“D”
Across
Corners
“D”
Protrusion
Length “F”
Combined Ordering Reference
(*Brass Metric)
ShroudCable
Gland
Weight
(Ozs)
StandardOptionGrooved Cone (X)Stepped Cone (W)
MetricThread Length (Metric) “E”NPTThread Length
(NPT) “E”
NPTMinMaxMinMaxMinMaxMinMaxMaxMaxSizeTypeOrdering
Suffix
16M1615.00.120.340.240.520.010.040.030.050.941.043.1016T3CDS1RAPVC366.35
20S16M2015.0½”0.78¾”0.120.340.240.520.010.040.030.050.941.043.1020S16T3CDS1RAPVC367.05
20SM2015.0½”0.78¾”0.240.460.370.630.010.040.030.050.941.043.1020ST3CDS1RAPVC367.05
20M2015.0½”0.78¾”0.260.550.490.820.020.040.030.051.201.323.0020T3CDS1RAPVC069.88
25SM2515.0¾”0.801″0.440.780.550.870.020.050.050.061.481.633.5025ST3CDS1RAPVC0915.52
25M2515.0¾”0.801″0.440.780.721.030.020.050.050.061.481.633.4925T3CDS1RAPVC0915.52
32M3215.01″0.981 ¼”0.671.030.931.330.020.050.060.081.811.993.5732T3CDS1RAPVC1122.22
40M4015.01 ¼”1.011 ½”0.871.261.101.590.020.060.060.082.172.383.6740T3CDS1RAPVC1532.10
50SM5015.01 ½”1.032″1.161.501.391.840.020.060.080.102.362.603.9650ST3CDS1RAPVC1839.51
50M5015.02″1.062 ½”1.401.731.592.090.020.060.080.102.763.044.1750T3CDS1RAPVC2156.44
63SM6315.02″1.062 ½”1.581.961.802.340.020.060.080.102.953.254.0463ST3CDS1RAPVC2361.02
63M6315.02 ½”1.573″1.862.202.152.590.020.060.080.103.153.464.1563T3CDS1RAPVC2562.79
75SM7515.02 ½”1.573″2.082.442.322.830.020.060.080.103.543.904.3575ST3CDS1RAPVC2890.65
75M7515.03″1.633 ½”2.332.672.633.090.020.060.100.123.944.334.7475T3CDS1RAPVC30117.46
90M9024.03 ½”1.694″2.623.093.003.560.030.060.120.164.534.985.4790T3CDS1RAPVC32171.78
100M10024.03 ½”1.694″2.993.583.393.990.030.060.120.165.005.505.05100T3CDS1RALSF33175.31
115M11524.04″1.735″3.393.854.004.340.030.060.120.165.435.986.35115T3CDS1RALSF34272.32
130M13024.05″1.843.824.524.344.850.030.060.120.166.186.806.82130T3CDS1RALSF35344.98
Dimensions displayed in inches unless otherwise stated

Download Spec Sheet

Download

CMP T3CDS | EUTEX T3CDS Technical Info

CMP T3CDS are explosive atmosphere barrier double-seal universal cable glands that are suitable for terminating all types of armored cables. Certified by ATEX for safe glanding of cables in Class 1, Zone 1, potentially explosive atmospheres, they feature a metal-to-metal sealing system that reduces costs, risks, and installation time.

This type of cable gland is manufactured to meet a wide array of standards, specifications, and codes. Examples include:

ATEX Certificates

  • CML 18ATEX1326X
  • CML 18ATEX4318X

Approvals

  • LRS: 01/00172 (E3)
  • DNV: TAE00000Y
  • ABS: 20-LD1948801-PDA
  • BV: 43180/A1BV

UL Compliance Standards

  • UL 514B Ed 5
  • UL 50 Ed 11
  • UL 2225 Ed 4
  • UL60079-0, 1, 7

IECEx Certificates

  • IECEx SIR 13.0027X
  • IECEx CML 18.0183X

UL Certificates

  • E200163

Code of Protection

  • Class I, Zone 1, AEx e II

Compliance Standards

  • IEC 60079-0,1,7,15,31

The Triton CDS cable gland utilizes a double-sealing mechanism, which includes an integral protected deluge seal and a controlled outer load-retention seal. It’s designed with a three-step installation process.

Available construction materials include brass, electroless nickel-plated brass, stainless steel, and aluminum constructions. EUTEX International’s standard offering is nickel-plated brass. Optional accessories include locknuts, earth tags, serrated washers, entry thread seals, shrouds, and ingress discs.

Standard cable operating environments are -60°C to +130°C, whereas ThermEx options are 20°C to 200°C. Many applications can benefit from integrating Triton CDS cable glands into their processes.

  • Aerospace
  • Defense
  • Chemical
  • Mining
  • Minerals & Metals
  • Commercial Construction
  • Downstream Hydrocarbons
  • Food & Beverage
  • Industrial Energy
  • Onsite Utilities

  • Industrial Machinery
  • Laboratory and R&D
  • Life Sciences
  • Medical
  • Marine
  • Oil & Gas
  • Packaging
  • Power
  • Pulp & Paper
  • Textiles
  • Water & Wastewate

Your Explosive Cable Gland Source

EUTEX International is a leading provider of electric cables and accessories for demanding industrial use. With an ISO 9001:2015-certified Quality Management System, every product we supply is guaranteed to be durable, effective, and of the highest quality. Strategically positioned locations worldwide enable us to deliver the electrical products you need on time and within budget.

Feel free to contact us about Triton cable gland products. Our experts are standing by to answer your questions.

Technical

Design SpecificationBS 6121:Part 1:1989, IEC 62444, EN 62444
Mechanical Classifications*Impact = Level 8, Retention = Class D
Enclosure ProtectionIK10 to IEC 62262 (20 joules) Brass & Stainless Steel only
Electrical Classifications*Category B (Category A when used with braid, tape or pliable wire armour cables)
ATEX CertificateSIRA13ATEX1073X
SIRA13ATEX4079X
Code of ProtectionII 2G,II 1D, Ex d IIC Gb, Ex e IIC Gb, Ex ta IIIC Da,
II 3G Ex nR IIC Gc, I M2, Ex d I Mb, Ex e I Mb
Compliance StandardsEN60079-0,1,7,15,31
IECEx CertificateIECEx SIR 13.0028X
IECEx SIM 14.0007X
Code of ProtectionEx d IIC Gb, Ex e IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da, Ex d I Mb, Ex e I Mb
Compliance StandardsIEC 60079-0,1,7,15,31
cCSAus Certificate (20s16 – 90)1310517
CSAus Code of ProtectionClass I, Div 2, Groups A,B,C and D, Class II, Div 2, Groups E,F and G, Class III, Enclosure
Type 3, 4 and 4X,
Class I, Zone 1, AEx e II, AEx nR II
cCSA Code of ProtectionClass I, Div 2, Groups A,B,C and D, Class II, Div 2, Groups E,F and G, Class III, Enclosure
Type 3, 4 and 4X,
Ex d IIC, Ex e IIC, Ex nR II
Compliance StandardsCAN/CSA-C22.2 No 0, 18, 25, 30, 94, 174, CAN/CSA-E60079-0, 1, 7,
ANSI/UL 514B Ed 5, ANSI/UL 50 Ed 11, ANSI/UL 2225 Ed 4, UL60079-0, 1, 7
UL Certificate (20s16 – 90)E200163
Code of ProtectionClass I, Zone 1, AEx e II
Compliance StandardsUL514B
EAC Certificate (Formerly GOST R, K & B)C-GB.AA87.B.00487
UkrSEPROUA.TR.047.C.0644-15
NEPSI CertificateGYJ13.1141X , GYJ13.1283X
CCOE / PESO (India) CertificateP333688
INMETRO CertificateTÜV 11.0374X
RETIE Certificate03866
Marine ApprovalsLRS: 01/00172 (E4), DNV: TAE00000Y, ABS: 14-LD234401A-4-PDA, BV: 43180/A1
Ingress Protection Rating **IP66, IP67 & IP68
Deluge Protection ComplianceDTS01 : 91
Cable Gland MaterialBrass, Electroless Nickel Plated Brass, Aluminium, Stainless Steel
Seal MaterialCMP SOLO LSF Halogen Free Thermoset Elastomer
Cable TypeSingle Wire Armour (SWA), Aluminium Wire Armour (AWA), Pliable Wire Armour (PWA), Steel Tape Armour (STA), Aluminium Strip Armour (ASA), Screened Flexible (EMC) Wire Braid (e.g. CY/SY), Wire Braid Armour (e.g. SWB)
Armour ClampingReversible Armour Cone & AnyWay Universal Clamping Ring
Sealing TechniqueInner Bedding Sealing Ring: Compensating Displacement Seal (CDS), Outer Sheath Sealing Ring : Load Retention Seal (LRS)
Sealing Area(s)Cable Inner Bedding & Outer Cable Sheath
Optional AccessoriesLocknuts, Earth Tags, Serrated Washers, Entry Thread Seals, Shrouds,Ingress Discs
Optional Installation ToolsSpanners, Armour Former Tool

Product Table

Metric

Cable Gland SizeAvailable Entry Threads “C” (Alternate Metric Thread Lengths Available)Cable
Bedding
Diameter
“A”
Overall
Cable
Diameter
“B”
Armour RangeAcross
Flats
“D”
Across
Corners
“D”
Protrusion
Length “F”
Combined Ordering Reference
(*Brass Metric)
ShroudCable
Gland
Weight
(Kgs)
StandardOptionGrooved Cone (X)Stepped Cone (W)
MetricThread Length (Metric) “E”NPTThread Length
(NPT) “E”
NPTMinMaxMinMaxMinMaxMinMaxMaxMaxSizeTypeOrdering
Suffix
16M1615.03.18.66.113.10.31.00.81.2524.026.478.716T3CDS1RAPVC360.18
20S16M2015.0½”19.9¾”3.18.66.113.10.31.00.81.2524.026.478.720S16T3CDS1RAPVC360.20
20SM2015.0½”19.9¾”6.111.69.515.90.31.00.81.2524.026.478.720ST3CDS1RAPVC360.20
20M2015.0½”19.9¾”6.513.912.520.90.41.00.81.2530.533.676.220T3CDS1RAPVC060.28
25SM2515.0¾”20.21″11.119.914.022.00.41.21.251.637.541.388.825ST3CDS1RAPVC090.44
25M2515.0¾”20.21″11.119.918.226.20.41.21.251.637.541.388.725T3CDS1RAPVC090.44
32M3215.01″25.01 ¼”17.026.223.733.90.41.21.62.046.050.690.732T3CDS1RAPVC110.63
40M4015.01 ¼”25.61 ½”22.032.127.940.40.41.61.62.055.060.593.240T3CDS1RAPVC150.91
50SM5015.01 ½”26.12″29.538.135.246.70.41.62.02.560.066.0100.750ST3CDS1RAPVC181.12
50M5015.02″26.92 ½”35.644.040.453.00.61.62.02.570.177.1105.850T3CDS1RAPVC211.60
63SM6315.02″26.92 ½”40.149.945.659.40.61.62.02.575.082.5102.563ST3CDS1RAPVC231.73
63M6315.02 ½”39.93″47.255.954.665.80.61.62.02.580.088.0105.463T3CDS1RAPVC251.78
75SM7515.02 ½”39.93″52.861.959.072.00.61.62.02.590.099.0110.675ST3CDS1RAPVC282.57
75M7515.03″41.53 ½”59.167.966.778.40.61.62.53.0100.0110.0120.375T3CDS1RAPVC303.33
90M9024.03 ½”42.84″66.678.676.290.30.81.63.154.0115.0126.5138.990T3CDS1RAPVC324.87
100M10024.03 ½”42.84″76.090.986.1101.40.81.63.154.0127.0139.7128.2100T3CDS1RALSF334.97
115M11524.04″44.05″86.097.9101.5110.20.81.63.154.0138.0151.8161.3115T3CDS1RALSF347.72
130M13024.05″46.897.0114.9110.2123.20.81.63.154.0157.0172.7173.3130T3CDS1RALSF359.78
Dimensions displayed in millimeters unless otherwise stated

Imperial

Cable Gland SizeAvailable Entry Threads “C” (Alternate Metric Thread Lengths Available)Cable
Bedding
Diameter
“A”
Overall
Cable
Diameter
“B”
Armour RangeAcross
Flats
“D”
Across
Corners
“D”
Protrusion
Length “F”
Combined Ordering Reference
(*Brass Metric)
ShroudCable
Gland
Weight
(Ozs)
StandardOptionGrooved Cone (X)Stepped Cone (W)
MetricThread Length (Metric) “E”NPTThread Length
(NPT) “E”
NPTMinMaxMinMaxMinMaxMinMaxMaxMaxSizeTypeOrdering
Suffix
16M1615.00.120.340.240.520.010.040.030.050.941.043.1016T3CDS1RAPVC366.35
20S16M2015.0½”0.78¾”0.120.340.240.520.010.040.030.050.941.043.1020S16T3CDS1RAPVC367.05
20SM2015.0½”0.78¾”0.240.460.370.630.010.040.030.050.941.043.1020ST3CDS1RAPVC367.05
20M2015.0½”0.78¾”0.260.550.490.820.020.040.030.051.201.323.0020T3CDS1RAPVC069.88
25SM2515.0¾”0.801″0.440.780.550.870.020.050.050.061.481.633.5025ST3CDS1RAPVC0915.52
25M2515.0¾”0.801″0.440.780.721.030.020.050.050.061.481.633.4925T3CDS1RAPVC0915.52
32M3215.01″0.981 ¼”0.671.030.931.330.020.050.060.081.811.993.5732T3CDS1RAPVC1122.22
40M4015.01 ¼”1.011 ½”0.871.261.101.590.020.060.060.082.172.383.6740T3CDS1RAPVC1532.10
50SM5015.01 ½”1.032″1.161.501.391.840.020.060.080.102.362.603.9650ST3CDS1RAPVC1839.51
50M5015.02″1.062 ½”1.401.731.592.090.020.060.080.102.763.044.1750T3CDS1RAPVC2156.44
63SM6315.02″1.062 ½”1.581.961.802.340.020.060.080.102.953.254.0463ST3CDS1RAPVC2361.02
63M6315.02 ½”1.573″1.862.202.152.590.020.060.080.103.153.464.1563T3CDS1RAPVC2562.79
75SM7515.02 ½”1.573″2.082.442.322.830.020.060.080.103.543.904.3575ST3CDS1RAPVC2890.65
75M7515.03″1.633 ½”2.332.672.633.090.020.060.100.123.944.334.7475T3CDS1RAPVC30117.46
90M9024.03 ½”1.694″2.623.093.003.560.030.060.120.164.534.985.4790T3CDS1RAPVC32171.78
100M10024.03 ½”1.694″2.993.583.393.990.030.060.120.165.005.505.05100T3CDS1RALSF33175.31
115M11524.04″1.735″3.393.854.004.340.030.060.120.165.435.986.35115T3CDS1RALSF34272.32
130M13024.05″1.843.824.524.344.850.030.060.120.166.186.806.82130T3CDS1RALSF35344.98
Dimensions displayed in inches unless otherwise stated